Wire Gauge Calculator⚡

Calculate the correct electrical wire size based on current, distance, voltage drop, conductor material, and NEC derating factors.
This wire gauge calculator supports AWG and metric wire sizes and helps electricians, engineers, and DIY users choose the safest cable size for their circuits.

Dual-check calculation for NEC Ampacity and Voltage Drop requirements.

Core Circuit Requirements
Low-voltage DC is sized by voltage drop, not ampacity — the conductor is almost always larger than the current alone would suggest. Marine and RV practice (ABYC E-11) allows 3% for critical circuits such as bilge pumps, navigation lights and electronics, and 10% for non-critical loads.
Advanced NEC Derating Factors
Recommended Wire Size
-- AWG
Awaiting Input
0% 3% 5% 10% Drop
Why this size? (Dual Check)
Ampacity Requirement-- AWG
Voltage Drop Requirement-- AWG
Final Selected-- AWG
Estimated Performance
Voltage Drop0.00 V
Voltage Drop %0.00 %
Voltage at End0.00 V
Compare Materials
MaterialRecommended WireEst. Drop %
Alternative Wire Sizes
Wire SizeDrop %Voltage LostStatus
Quick Simulations
Show Engineering Details

How to Calculate Wire Gauge

Sizing electrical wire correctly is critical for both safety and performance. A proper wire gauge calculator must execute a Dual-Check System. First, it determines the Ampacity Requirement to ensure the wire will not overheat and melt under the required load. Second, it calculates the Voltage Drop Requirement to ensure the equipment at the end of the wire receives enough voltage to operate efficiently. The calculator must select whichever wire gauge is larger between these two tests.

Wire Gauge Formula Explained

The standard professional formulas used to calculate both variables are based directly on the National Electrical Code (NEC):

  • Corrected Ampacity: Required Current = (Load Current × Safety Factor) / (Temperature Factor × Conduit Fill Factor)
  • DC & Single-Phase AC Voltage Drop: VD = (2 × Length × Current × Resistance) / 1000
  • Three-Phase AC Voltage Drop: VD = (1.732 × Length × Current × Resistance) / 1000

Once Voltage Drop (VD) is calculated, you find the percentage by dividing the VD by the source voltage and multiplying by 100.

Ampacity vs Voltage Drop

Ampacity is purely a safety constraint. It defines the maximum amount of electrical current a wire can carry before its insulation begins to melt, which is a severe fire hazard. Voltage Drop is a performance and efficiency constraint. As power travels over long distances, wire resistance causes voltage to "leak" away as heat. If the voltage drops too low, electronics may shut down, and motors will pull excess current, causing them to overheat and fail prematurely.

Copper vs Aluminum Wire Size

The material of your conductor significantly impacts the required wire size. Copper is an exceptional conductor with very low electrical resistance, allowing you to use a thinner wire gauge for heavy loads. Aluminum has higher resistance and is less conductive, but it is vastly lighter and less expensive. As a general rule in the electrical industry, if you switch from a copper wire to an aluminum wire, you must upsize the wire by one or two full gauge sizes to handle the identical ampacity and maintain the same voltage drop limit.

Single Phase vs Three Phase Wire Sizing

The type of power system you are running alters how voltage drops over a distance. In a standard Single-Phase circuit (like a 120V residential outlet), power must travel down the hot wire and all the way back via the neutral wire, which is why the formula uses a multiplier of 2. In a Three-Phase circuit, the power delivery is staggered across three wires, making it much more efficient. As a result, the calculation uses a smaller multiplier of 1.732 (the square root of 3), meaning you can often use a slightly smaller wire size for 3-phase equipment than you could for single-phase equipment of the same amperage.

Wire Gauge Chart (AWG to mm²)

While the United States and North America use the American Wire Gauge (AWG) system, most of the rest of the world uses cross-sectional area measured in square millimeters (mm²). Here is a quick reference conversion chart for standard sizes:

American Wire Gauge (AWG)Metric Equivalent (Approx. mm²)Max Copper Ampacity (75°C)
14 AWG2.08 mm²20 Amps
12 AWG3.31 mm²25 Amps
10 AWG5.26 mm²35 Amps
8 AWG8.37 mm²50 Amps
6 AWG13.3 mm²65 Amps
4 AWG21.2 mm²85 Amps

What Wire Size Do I Need?

The exact wire size you need depends entirely on your specific parameters. For a short, 15-Amp household lighting circuit, a 14 AWG copper wire is perfectly adequate. However, if you are running a 50-Amp Subpanel feeder line 150 feet out to a detached garage, you must account for the severe voltage drop over that distance, which may force you to use a heavy-duty 4 AWG or 2 AWG wire to remain within the safe 3% NEC limit. Always use a dual-check wire gauge calculator to verify your exact needs before purchasing wire.

The Breaker Does Not Decide Your Wire Size — the Distance Does

Ask what size wire a 20 amp circuit needs and almost everyone answers 12 AWG. Run that circuit 100 feet down a garden to a workshop and 12 AWG is the wrong answer: the drop is 7.92 V — 6.60% — and the tools at the far end see 112 volts instead of 120. Stepping to 10 AWG still misses at 4.14%. You need 8 AWG, two full sizes above the table answer.

Ampacity and voltage drop are two separate questions. Ampacity asks whether the conductor will overheat; it depends only on current. Voltage drop asks whether enough voltage survives the run; it depends on distance. The correct wire size is whichever of the two demands the thicker conductor, and on any run over about 50 feet that is usually voltage drop.

Wire size calculator - copper building wire in six AWG gauges with wire strippers and a brass AWG gauge plate on a workbench
Copper building wire in six AWG gauges. The gauge number falls as the conductor gets thicker — 4 AWG is far heavier than 14 AWG.

The calculator above runs both checks at once and returns the larger result, so you never have to remember which one governs.

What Size Wire Do I Need? Amps to AWG at a Glance

Minimum copper and aluminium conductor for each common breaker size, based on the NEC 75°C ampacity column. These are the starting sizes — check the run length before you buy, because distance frequently pushes the answer one or two gauges larger.

Breaker / LoadCopper AWGAluminium AWGTypical use
15 A14 AWGLighting circuits
20 A12 AWG10 AWGKitchen and general outlets
30 A10 AWG8 AWGDryer, water heater, RV hookup
40 A8 AWG6 AWGElectric range, small subpanel
50 A8 AWG (6 AWG at 60°C)6 AWGRange, EV charger, welder, RV
60 A6 AWG4 AWGSubpanel, hot tub
70 A4 AWG3 AWGLarger subpanel
100 A3 AWG (4 AWG for a dwelling service)1 AWG (2 AWG service)Garage feeder, small service
125 A1 AWG1/0 AWGLarge subpanel
150 A1/0 AWG2/0 AWGService entrance
200 A3/0 AWG (2/0 for a dwelling service)4/0 AWGMain service entrance

Two footnotes that trip people up. NEC 240.4(D) caps the small conductors regardless of what the ampacity table says: 14 AWG is limited to 15 A, 12 AWG to 20 A, 10 AWG to 30 A. And NEC 310.12 lets dwelling service and main feeder conductors run smaller than the general table — which is why a 200 amp house service is commonly 2/0 copper rather than 3/0.

How to Calculate Wire Size for Amps

Two checks, then take the larger conductor.

Check one — ampacity. Find the smallest conductor whose rated ampacity meets or exceeds your load. If the load is continuous (three hours or more, such as an EV charger), size for 125% of it. Then derate for ambient temperature and for more than three current-carrying conductors in a raceway.

Check two — voltage drop. Work out the drop over the run and step up until it falls inside your limit. The NEC recommends 3% on a branch circuit and 5% across feeder plus branch combined. Our Voltage Drop Calculator shows this in detail, and the Cable Size Calculator covers the metric side.

A worked example: a 50 amp subpanel at 240 V. Ampacity says 6 AWG, and at 120 feet that is genuinely fine — 2.45%. Push the same feeder to 200 feet and it reaches 4.09%, so the conductor has to go up to 4 AWG. Nothing about the load changed; only the distance did.

AWG Wire Size Chart: Amps, mm² and Resistance

American Wire Gauge runs backwards — a smaller number means a thicker conductor, and every three gauges roughly doubles the cross-sectional area. Ampacity below is copper at 75°C.

AWGmm²Copper amps (75°C)Ω / km
14 AWG2.082010.32
12 AWG3.31256.50
10 AWG5.26354.07
8 AWG8.37502.55
6 AWG13.3651.61
4 AWG21.2851.01
3 AWG26.71000.80
2 AWG33.61150.64
1 AWG42.41300.50
1/0 AWG53.51500.40
2/0 AWG67.41750.32
3/0 AWG85.02000.25
4/0 AWG107.22300.20

Working from metric drawings? The AWG to mm² Converter handles sizes between these rows.

Wire Size for 12V DC, 24V and 48V Systems

Low-voltage DC follows completely different rules, and this is where most sizing mistakes happen. At 12 volts, a 3% allowance is just 0.36 V — so voltage drop, not ampacity, decides the conductor almost every time.

Take a 12 V circuit pulling 80 amps over 15 feet, a typical car audio amplifier run. Ampacity alone allows 4 AWG. Hold the drop to 3% and you need 1/0 AWG — three sizes heavier. Switch the calculator above to DC and the 12 V preset to see it.

Marine and RV practice (ABYC E-11) splits the limit by criticality: 3% for bilge pumps, navigation lights, electronics and panel feeds, and 10% for non-critical loads such as cabin lighting or accessory sockets. Applying 3% everywhere on a boat produces absurdly heavy cable; applying 10% to a bilge pump is unsafe.

The same logic drives solar and battery work. A battery-to-inverter run is short but carries enormous current, so it is sized almost entirely by drop — 100 amps over six feet at 12 V still needs 3 AWG. Moving a system from 12 V to 24 V halves the current and quarters the drop for the same power, which is exactly why larger off-grid installations run at 48 V. For the storage side, see the Battery Backup Calculator.

How Many Amps Can Each Gauge Handle?

The reverse lookup — you have the wire and want to know what it will safely carry. Copper, 75°C column, before any derating:

14 AWG → 15 A

Rated 20 A but capped at 15 A by NEC 240.4(D).

12 AWG → 20 A

Rated 25 A, capped at 20 A on branch circuits.

10 AWG → 30 A

Rated 35 A, capped at 30 A. Dryers and water heaters.

8 AWG → 50 A

No small-conductor cap above 10 AWG.

6 AWG → 65 A

Subpanels, hot tubs, larger EV chargers.

4 AWG → 85 A

Feeders and 100 A dwelling services.

The NEC Rules That Change the Answer

Four adjustments turn a table lookup into a real answer:

Continuous loads (210.19). Anything drawing full current for three hours or more must be sized at 125%. A 40 amp EV charger is therefore a 50 amp calculation.

Terminal temperature rating (110.14(C)). You may only use the 75°C column if the breaker and lugs are rated for 75°C. Much residential equipment is 60°C rated, which is why a 50 amp circuit sometimes needs 6 AWG rather than 8 AWG.

Bundling and ambient heat (310.15). More than three current-carrying conductors in one raceway, or a hot attic, forces a derating factor that can cost you a full gauge size.

Aluminium needs upsizing. Roughly 1.6× the resistivity of copper for the same area, so plan on one to two sizes larger. It is lighter and cheaper on long feeders, but the terminations demand the correct antioxidant compound and torque. For the fault side of the design, check the Short Circuit Current Calculator.

Manufacturers publish the real numbers for the specific cable you are buying — conductor makers such as Prysmian list ampacity, insulation temperature rating and dimensions for every construction, and those beat any generic chart when the margin is tight.

More tools of this kind are collected in our engineering calculators hub.

Frequently Asked Questions

How do I calculate wire gauge?

To correctly calculate wire gauge, you must perform a dual-check. First, calculate the ampacity required to safely carry the current without overheating, factoring in continuous loads and temperature derating. Second, calculate the voltage drop over the intended distance to ensure it remains under 3%. You must select the thicker wire size dictated by these two calculations.

What wire size do I need for my current and distance?

The required wire size depends on the load current, system voltage, and total cable length. For short distances, standard ampacity rules apply (e.g., 12 AWG for 20 Amps). However, as distance increases, wire resistance causes voltage drop. For long runs, you must often step up to a thicker wire (like 10 AWG or 8 AWG) to maintain efficient power delivery.

How much voltage drop is acceptable?

The National Electrical Code (NEC) recommends a maximum voltage drop of 3% for individual branch circuits or feeder circuits, and a total combined voltage drop (feeder plus branch circuit) of no more than 5%.

Is copper better than aluminum wire?

Copper is a superior electrical conductor with lower resistance, allowing you to use a thinner wire for a given load. Aluminum is less conductive and requires a thicker wire (usually one or two gauge sizes larger) for the same load. However, aluminum is significantly lighter and more cost-effective, making it very popular for long, heavy feeder runs.

What is the difference between AWG and mm²?

AWG stands for American Wire Gauge, the standard electrical wire sizing system used in North America, where a smaller number represents a thicker wire. The rest of the world typically measures wire by its physical cross-sectional area in square millimeters (mm²), where a larger number indicates a thicker wire.

Should wire size be based on ampacity or voltage drop?

Wire size must be based on both. Ampacity dictates the minimum safe size to prevent the wire from overheating and creating a fire hazard. Voltage drop dictates the minimum size needed to efficiently deliver power over a distance so equipment functions properly. You must always choose the larger (thicker) wire size required between the two calculations.

What wire gauge do I need for a 20 amp circuit?

For a standard 20 amp circuit, the National Electrical Code (NEC) requires a minimum of 12 AWG copper wire. However, if the wire run is exceptionally long (typically over 50-100 feet depending on voltage), you may need to upgrade to 10 AWG to prevent excessive voltage drop.

Does wire length affect gauge size?

Yes, wire length heavily impacts the required gauge size. The longer a wire is, the more electrical resistance it has. To push current over a long distance without losing voltage (voltage drop) or creating dangerous heat, you must use a thicker wire (a lower AWG number).

Why do I need a thicker wire for continuous loads?

The NEC defines a continuous load as any device that runs at maximum current for 3 hours or more (like an EV charger or a heater). Continuous loads generate persistent heat, so you must size the wire to handle 125% of the actual load to prevent the insulation from melting.

What size wire do I need for a 50 amp breaker?

For a 50 amp breaker, 8 AWG copper is the minimum where the terminations are rated 75°C, and 6 AWG copper where they are only rated 60°C, which is common on residential equipment. Aluminium needs 6 AWG. Those figures hold for short runs only. A 50 amp feeder at 240 V stays inside 3% voltage drop on 6 AWG out to roughly 150 feet, but at 200 feet it reaches 4.09% and must move up to 4 AWG.

What size wire is needed for a 100 amp service?

A 100 amp dwelling service is normally 4 AWG copper or 2 AWG aluminium. That is smaller than the general ampacity table suggests because NEC 310.12 permits reduced conductors for dwelling services and main feeders. For a 100 amp feeder that is not a dwelling service, size from the standard table instead, which calls for 3 AWG copper.

What size wire for a 200 amp service?

A 200 amp dwelling service typically uses 2/0 copper or 4/0 aluminium under the NEC 310.12 dwelling allowance. Outside that allowance, the general table requires 3/0 copper. Because service conductors are usually short, ampacity governs rather than voltage drop, but always confirm the terminal temperature rating on the meter base and main breaker before settling on a size.

How many amps can 10 gauge wire handle?

10 AWG copper is rated 35 amps in the NEC 75°C column, but NEC 240.4(D) caps it at 30 amps for overcurrent protection, so a 30 amp breaker is the practical maximum. That makes it the standard choice for electric dryers, water heaters and 30 amp RV hookups. Over long runs voltage drop may still require 8 AWG even though the ampacity is adequate.

What size wire do I need for a 12 volt system?

Low-voltage DC is sized by voltage drop rather than ampacity, because a 3% allowance at 12 volts is only 0.36 V. An 80 amp car audio run over 15 feet needs 1/0 AWG even though ampacity alone would permit 4 AWG. Marine and RV practice under ABYC E-11 allows 3% for critical circuits such as bilge pumps and navigation lights, and 10% for non-critical loads.

Figures follow standard NEC ampacity tables and assume normal operating conditions. Actual requirements vary with insulation type, ambient temperature, conductor bundling, terminal ratings and local amendments. Use these results for planning and have a licensed electrician verify any final design before installation.

Other Tools in this Category

Resistor Voltage Drop Calculator

RPM to Speed Calculator

Torque Calculator

Transformer Load Calculator

Motor Current Calculator

Short Circuit Current Calculator

Generator Sizing Calculator

Energy Consumption Calculator

kW to kVA Calculator

Battery Backup Calculator

Cable Size Calculator

Power Factor Correction Calculator

Ohm’s Law Calculator

AWG to mm² Converter

Resistor Color Code Calculator

Voltage Drop calculator

Scroll to Top